VICTOR 6412E Explosion-proof Clamp Ground Resistance Tester Auto Range

$ 150.94

Availability: 31 in stock
  • Brand: VICTOR
  • MPN: VICTOR 6412E
  • Condition: New

    Description

    VICTOR 6412E Explosion-proof Clamp Ground Resistance Tester Auto Range
    Notice:
    The standard package don't include batteries.
    Because,the international air shipping forbid to ship liquid,powder and batteries,
    we can not put them in the package box.
    Hope you can understand buy them in your local store or supermarket.
    At the same time, please forgive us that we are unable to provide the English user manual.
    If you need it, please contact the customer service after purchase.
    Thanks for your support!
    The VICTOR 6412E explosion-proof clamp grounding resistance meter has passed the explosion-proof certification and meets the requirements of GB3836-2000 "Electrical Equipment for Explosive Gas Environments". Its explosion-proof mark is Ex ia Ⅱ BT3Ga. The shell of the clamp meter is made of anti-static engineering plastic, which is safer and more reliable. It can be used in the corresponding flammable and explosive environment.
    VICTOR 6412E clamp-on ground resistance meter is widely used in ground resistance measurement and loop resistance measurement in electric power, telecommunications, meteorology, oil fields, construction and industrial electrical equipment. When measuring a grounding system with a loop, there is no need to disconnect the grounding down conductor, and no auxiliary electrode is needed, which is safe and fast. It can measure ground faults that cannot be measured by traditional methods, and can be applied to occasions that cannot be measured by traditional methods, because the clamp-on ground resistance meter measures the combined value of grounding body resistance and ground lead resistance.
    Measurement range
    Resolution force
    Accuracy
    0.010Ω-0.099Ω
    0.001Ω
    ±(1%+0.01Ω)
    0.10Ω-0.99Ω
    0.01Ω
    ±(1%+0.01Ω)
    1.0Ω-49.9Ω
    0.1Ω
    ±(1%+0.1Ω)
    50.0Ω-99.5Ω
    0.5Ω
    ±(1.5%+0.5Ω)
    100Ω-199Ω

    ±(2%+1Ω)
    200Ω-395Ω

    ±(5%+5Ω)
    400-590Ω
    10Ω
    ±(10%+10Ω)
    600Ω-1200Ω
    30Ω
    ±(25%+30Ω)
    Resistance range
    0.01Ω-1200Ω
    Resistance resolution
    0.001Ω
    data storage
    99 groups
    Audible alarm
    "Beep--beep--beep--" alarm sound, press AL key to turn on and off
    Alarm threshold setting range
    1-199Ω;
    power supply
    6VDC (4 AA alkaline dry batteries)
    Working temperature and humidity
    -20℃-55℃; 10%RH-90%RH
    LCD Monitor
    4-digit LCD digital display, length and width 47mm×28.5mm
    Jaw size
    65mm×32mm
    Jaw opening size
    35mm
    Clamp meter quality
    1160g (including battery)
    Clamp meter size
    Long jaw: length, width and thickness 285mm×85mm×56mm
    Explosion-proof mark
    Ex ia Ⅱ BT3Ga
    Protection level
    Double insulation
    Structural features
    Clamp CT
    Shift
    Fully automatic gear shift
    Single measurement time
    0.5 seconds
    Resistance measurement frequency
    >1KHz